๐ŸŽ‰ Use code WELCOME10 for 10% off your first orderโšก Free shipping on orders above โ‚น499๐Ÿญ Bulk orders? Get special B2B pricing โ€” Call us nowโœ… GST invoices on every order๐Ÿšš Pan-India delivery in 3-5 business days๐Ÿ”ฅ New ABB switchgear products now in stock๐ŸŽ‰ Use code WELCOME10 for 10% off your first orderโšก Free shipping on orders above โ‚น499๐Ÿญ Bulk orders? Get special B2B pricing โ€” Call us now
Guide20 August 2026 ยท by TEKTOW

Contact Resistance Test on a VCB: What the Micro-Ohm Reading Tells You

Why Measure It

Every closed contact pair in a breaker has a small electrical resistance. If contacts wear, oxidise, or loosen, that resistance rises, and under load it turns into heat. A micro-ohm measurement puts a number on it.

How the Test Works

A micro-ohmmeter passes a DC test current, commonly 100 A or more, through the closed main circuit of each pole and measures the voltage drop, then calculates resistance in micro-ohms. Testing is done with the breaker closed, isolated, and earthed per site safety rules.

Reading the Results

  • Compare each pole with the manufacturer limit or the commissioning baseline.
  • Compare the three poles with each other - a pole noticeably higher than the others deserves investigation.
  • Track readings over time, since a rising trend matters even if the value is still within limits.

What a High Reading Suggests

Common causes are worn or contaminated contacts, loose primary connections, or insufficient contact pressure. Cleaning, tightening, or replacing the affected parts is the usual fix. Pair the result with a thermal imaging survey for extra confidence.